Arifiani, Nur Fajri and Hadiwidodo, Mochtar (2007) Evaluasi Desain Instalasi Pengolahan Air PDAM Ibu Kota Kecamatan Prambanan Kabupaten Klaten. Jurnal PRESIPITASI, 3 (2). pp. 78-85. ISSN 1907-187X
| PDF - Published Version 83Kb |
Abstract
To supply good water quality, quantity, and continuity is needed an Water Treatment Plant (WTP). The unit process and operation is dependent on quality of water resources. WTP in Klaten Unit Prambanan had a design flow of 20 L/s and had quality of water resources which is more than water parameter regulation. There are ferrous (3,36 mg/L), mangan (0,58 mg/L), colour (159 TCU), and bad odour. So, it is needed aeration, koagulation, flocculation, sedimentation, and filtration units to separate them. Quality of water efluent in this WTP is less than water parameter regulation. There are ferrous (0,18 mg/L) , mangan (0,21 mg/L), colour (3 TCU), and no odour. But, its need more improvement to optimalize reducing parameters.
Item Type: | Article |
---|---|
Uncontrolled Keywords: | Ferrous and Mangan Removal, Aeration |
Subjects: | T Technology > TD Environmental technology. Sanitary engineering |
Divisions: | Faculty of Engineering > Department of Environmental Engineering Faculty of Engineering > Department of Environmental Engineering |
ID Code: | 524 |
Deposited By: | Mr. Sugeng Priyanto |
Deposited On: | 07 Sep 2009 11:23 |
Last Modified: | 07 Sep 2009 11:23 |
Repository Staff Only: item control page