Setyoko, Bambang (2008) EVALUASI KINERJA HEAT EXCHANGER DENGAN METODE FOULING FAKTOR. TEKNIK, Vol. 29 (No. 2). pp. 148-153. ISSN ISSN 0852-1697
| PDF 200Kb |
Abstract
The performance of heat exchangers usually deteriorates with time as a result of accumulation of deposits on heat transfer surfaces. The layer of deposits represents additional resistance to heat transfer and causes the rate of heat transfer in a heat exchanger to decrease. The net effect of these accumulations on heat transfer is represented by a fouling factor Rf , which is a measure of the thermal resistance introduced by fouling. In this case, the type of fouling is the precipitation of solid deposits in a fluid on the heat transfer surface. The mineral deposits forming on the inner and the outer surfaces of fine tubes in the heat exchanger. The fouling factor is increases with time as the solid deposits build up on the heat exchanger surface. Fouling increases with increasing temperature and decreasing velocity. In this research, we obtain the coefisien clean overal 5,93 BTU/h.ft2.oF, Dirt factor 0,004 BTU/h.ft2 0F, Pressure drope in tube 2,84 . 10-3 Psi and pressure drope in shell 4,93 . 10-4 Psi.This result are less than the standard of parameter. Its means this Heat exchanger still clean relativity and can operate continoussly without cleaning. Key words : heat exchanger, fouling factor.
Item Type: | Article |
---|---|
Subjects: | T Technology > TJ Mechanical engineering and machinery |
Divisions: | Faculty of Engineering > Diploma in Mechanical Engineering Faculty of Engineering > Diploma in Mechanical Engineering |
ID Code: | 35384 |
Deposited By: | INVALID USER |
Deposited On: | 24 May 2012 14:05 |
Last Modified: | 24 May 2012 14:05 |
Repository Staff Only: item control page