ANALISA JARINGAN DISTRIBUSI SISTEM PENYEDIAAN AIR BERSIH KOTA BOYOLALI

SAMBODJA , KHUSNUL HUDA and Nasrullah, Ir and Budihardjo, M. Arief (1999) ANALISA JARINGAN DISTRIBUSI SISTEM PENYEDIAAN AIR BERSIH KOTA BOYOLALI. Project Report. Teknik Lingkungan, Semarang.

[img]
Preview
PDF - Published Version
8Kb

Abstract

Water pressure in pipe represent important factor in drinking water supply system. To earn to conduct water optimally, required enough pressure. That is between 10 until 80 mka. Drinking water supply system of Boyolali City in the year 2005 is not optimally yet. Because still exist pressures values outside of planning standard. According to simulation result with Epanet Version 2.0, minimum pressures at peak hour condition (at 07:00) is -1,83 m and maximum pressures is 106,70 m. But, raw water productions in the year 2005 still answer the demand of residents consume requirement. Mean produce per day is about 7.241,40 m3 /day and water consume is about 5.718,96 m3 /day. Thus, in distribution pipes network of clean water is need to repair to reduce the happening of water leakage because of big pressures. Distribution service of clean water in PDAM of Boyolali City after repaired to become better because yielded pressures fulfilling criterion of water pressures planning in distribution pipes network. According to simulation result with Epanet Version 2.0, minimum pressures at peak hour condition (at 07:00) is 8,10 m and maximum pressures is 69,90 m Key words : water supply, distribution pipe netw

Item Type:Monograph (Project Report)
Subjects:T Technology > TD Environmental technology. Sanitary engineering
T Technology > TA Engineering (General). Civil engineering (General)
Divisions:Faculty of Engineering > Department of Environmental Engineering
Faculty of Engineering > Department of Environmental Engineering
ID Code:18748
Deposited By:INVALID USER
Deposited On:04 Aug 2010 14:38
Last Modified:04 Aug 2010 14:38

Repository Staff Only: item control page